Sensor Types
                                
                                
                                    24 VDC Dry Contacts
                                
                             
                            
                                
                                    Detection Level for On
                                
                                
                                    > 2.25 mA (<5.3 kΩ)
                                
                             
                            
                                
                                    Detection Level for Off
                                
                                
                                    < 1.75 mA (>8.2 kΩ)
                                
                             
                            
                            
                                
                                    Wetting Voltage
                                
                                
                                    22.5Volts (±5%), current limited to 12.5 mA nomina
                                
                             
                            
                                
                                    Field Circuit Protection
                                
                                
                                    12.5 mA Current Limiting Circuit, Field wiring disconnect
                                
                             
                            
                                
                                    CHARM Power Req.
                                
                                
                                    18 mA max @ 24 VDC
                                
                             
                            
                                
                                    CHARM Heat Dissipation
                                
                                
                                    0.33 W
                                
                             
                            
                                
                                    Fault Detection Capable
                                
                                
                                    Guaranteed short circuit: <100 Ω, Guaranteed good status: 400 Ω to 40 kΩ, Guaranteed open circuit: > 75 kΩ
                                
                             
                            
                                
                                    Configurable Channel Type
                                
                                
                                    Dry contact or discrete state sensor changing <2 Hz