The LT-420 is a unique device used for water level indication on Section I boilers and other boiler feedwater applications.

The unit combines several standard features in order to satisfy modern boiler code requirements, and at same time address challenging aspects of water/steam level applications. ASME BPVC.I-2019 PG-60.1.1 requires a Remote Level Indicator (RLI), to continuously measure, transmit and display the water level in the control room. The RLI is a discrete system that monitors the water level, independent of the DCS. Paired with a GWR transmitter, the LT-420 provides a reliable solution for water level indication.

Features

  • 4-20mA Output Signal
  • Programmable Alarm & Trip Points from Guided Wave Radar
  • Serial Remote Display Signal – Optional Fiber Optic
  • Ability to power three remote indicators
  • 4 – Relays, 8 AMP per relay
  • ASME PG60.1.1.2 Code Compliant

Specifications

Chamber A-105 Extruded
Probe Guard 304 SS Sheet Metal
Probe Mounting Horizontal Probe Mounting
Probe Type Type 800
Probe Material TFE Insulated Probe, Metaflex Gasket Seal
Probe Gasket Spiral Wound
Rating 1000 PSI Steam Working Pressure, 550°F