Operating Temperature
                                
                                
                                    H2S: -40 °F to +122 °F (-40 °C to +50 °C)
O2 Depletion: -22 °F to +122 °F (-30 °C to +50 °C)
CO: -22 °F to +122 °F (-30 °C to +50 °C)
                                
                             
                            
                                
                                    Update Rate
                                
                                
                                    1 second to 60 minutes, user selectable
                                
                             
                            
                                
                                    Time Constant / Response
                                
                                
                                    H
2S: 
- T20 < 8 seconds
 - T50 < 10 seconds
 - T90 < 45 seconds
 
O
2: 
 
                             
                            
                                
                                    Detection Range
                                
                                
                                    H2S: Gas Concentration Level 0-100 ppm range
O2 Depletion: Gas Concentration Level 0-25 % by volume
CO: Gas Concentration Level 0-1,000 ppm range
                                
                             
                            
                                
                                    Power Supply
                                
                                
                                    Replaceable, intrinsically safe lithium-thionyl chloride power module with PBT polymer enclosure
                                
                             
                            
                                
                                    Antenna Type
                                
                                
                                    PBT/PC integrated omnidirectional antenna
                                
                             
                            
                                
                                    Humidity Range
                                
                                
                                    H2: 10-95 % Relative Humidity Non Condensing
O2: 10-95 % Relative Humidity Non Condensing
CO: 5-95 % Relative Humidity Non Condensing
                                
                             
                            
                                
                                    Enclosure Rating
                                
                                
                                    IP66 ingress protection (IP) filter
                                
                             
                            
                                
                                    Housing Material
                                
                                
                                    Low-copper aluminum (A360) or stainless steel
                                
                             
                            
                                
                                    Certifications/Approvals
                                
                                
                                    Intrinsically Safe, CSA Division 1, and ATEX/IECEx Zone 0
                                
                             
                            
                                
                                    Outputs
                                
                                
                                    IEC 62591 WirelessHART 2.4GHz DSSS. Optional discrete output to support local alarms
                                
                             
                            
                                
                                    Accuracy
                                
                                
                                    H2S: ± 3 ppm or 10 % of reading, whichever is greater
O2 Depletion:  ±Within 0.5 % of oxygen content of supply gas
CO: ± 6 ppm or 10 % of reading, whichever is greater